L3 JOVYATLAS SERIES UPS
JOVYSTAR Delta Series DELTA-XXXK
Model: DELTA-XXXK
For Monitor security system, Medical equipment and emergency escape equipment, Internet system and server equipment and similar applications.
- 7.5~125 kVA
- On-line double conversion
- Up to 6 units in parallel
- Full-load efficiency >90%
Specifications
| Item | Value |
|---|---|
| Capacity | 7.5/10/15/20/25/32/40/60/80/100/125 kVA |
| Operating mode | On-line continuous conversion |
| Connecting voltage | 3×400V/230V |
| Mains frequency | 50Hz/60Hz ±5% |
| Output voltage | 400V/230V 3ph., adj. to 380V/220V 3ph. |
| Output voltage tolerance | Static ±1% |
| Output power factor | 0.8 ind. |
| Overload | 125%-10 min, 200%-100 ms, 2000%-20 ms |
| Efficiency at 100% | >90% (10~15 kVA), >92% (20~125 kVA) |
| Crest factor | 3 |
| MTBF | >100,000 h |
| Temperature range | 0~40℃ |
| Protection degree | IP 20 |
| Parallel | Up to 6 units, redundant configuration |
| Interfaces | RS-232, RS-485, SNMP |
Applications
- Monitor security system
- Medical equipment and emergency escape equipment
- Internet system and server equipment
- Each type of plant equipment and industrial application
- Data processing and Telecommunications satellite system
- Those precise equipment and working conditions that do not allow shortage
Capacity
7.5/10/15/20/25/32/40/60/80/100/125 kVA
Product Features
- This means that the JOVYSTAR delta is the optimal solution, as great reliability of the systems is our top priority. Our entire organisation and 55 years of experience in power supply technology stand for this.
- The JOVYSTAR delta is a real on-line system (double conversion, permanent conversion),it therefore protects against all power faults and power failures.
- The JOVYSTAR delta is available from 8,5kVA-125kVA. In units up to 32kVA, the batteries for short autonomy periods can be integrated in the UPS housing. The display and operating elements ao the JOVYSTAR delta have been designed ergonomically.
- Output isolating transformer
- Input-output insulation (operating from inverter)
- Manual By-pass
- Low harmonic distortion rejected into the mains
- Automatic battery Test
- IGBT technology for high frequency commutation
- High crest factor
- Capability of supplying distorted loads, containing output voltage distortion
- up to 6 units in parallel redundant configuration
- RS 232 – RS 485 serial interfaces
- High instantaneous overload capability
- High MTBF (>150.000h)
- Low MTTR (<0,5h)
- High efficiency starting at 25% load
- Easy installation and maintenance; total accessibility from the front
- Reduced dimensions
- Easy to use and manage, with piloted start-up and friendly diagnostic
- SNMP
- Control software for WINDOWS®
- These systems are manufactured in accordance with the strict quality guidelines as defined by DIN ISO 9001.
Specification
Technical Data
- Connecting voltage: 3x400V/230V +/1%
- Mains frequency: 50Hz/60Hz+/-5%
- Output voltage: 400V/230V 3ph., adj. to 380V/220V 3ph.
- Tolerance of output voltage: static +/- 1%, dynamic if load
- Output frequency: alternation from 0 to 100% +/- 5%%
- battery operation 50Hz/60Hz +/-,001Hz
- mains operation synch. range is 2%
- Power factor (output): 0,8ind.
- Overload: 125%-10min. 200%-100ms 2000%-20ms
- Distortion
- Temperature range: 0℃ ~+40℃
- MTBF: >100000h
- Crest factor: 3
- Operating mode: on-line continuous conversion
- Computer interface: optional
- Dimensions UPS (WxHxD): 10-15kVA: 620mmx1150mmx660mm
- 20-40kVA: 620mmx1300mmx840mm
- 60-125kVA: 815mmx1620mmx630mm
- Dimensions battery (WxHxD): 10-15kVA: 470mmx1150mmx800mm
- 20-40kVA: 620mmx1300mmx800mm
- 60-125kVA: 910mmx1600mmx800mm
- Protection degree: IP 20
- Humidity class: F acc. DIN 40040
- Radio interference level: EN 50091-2
Performance dependent data
| Nom. output power | 10kVA | 15kVA | 20kVA | 25kVA | 32kVA |
|---|---|---|---|---|---|
| Input power nom. | 10,4kVA | 15,9kVA | 20,8kVA | 25,6kVA | 32,6kVA |
| Input power max. | 12,5kVA | 18,7kVA | 24,9kVA | 30,5kVA | 39,5kVA |
| Current coms. nom. | 15A | 23A | 30A | 37A | 47A |
| Current coms. max. | 18A | 27A | 36A | 44A | 57A |
| Efficiency at 100% | >90% | >90% | >92% | >92% | >92% |
| Inverter-input power | 8,9kW | 13,3kW | 17,8kW | 22,2 | 27,8kW |
| Noise level (EN 50091) | <55dB(A) | <55dB(A) | <55dB(A) | >55dB(A) | <55dB(A) |
| Heat dissipation | 0,89kW | 1,33kW | 1,78kW | 1,74kW | 2,22kW |
| Cabinets using batt. 10min | 1 | 1 | 1 | 2 | 3 |
| Weight incl. batt. for 10min. | 420kg | 546kg | 761kg | 877kg | 710kg |
| Cabinets using batt. 30min. | 1 | 3 | 2 | 3 | 3 |
| Weight incl. batt. 30min. | 444kg | 662kg | 861kg | 881kg | 1181kg |
| Weight UPS without battery | 250kg | 310kg | 330kg | 350kg | 400kg |
Performance dependent data
| Nom. output power | 40kVA | 60kVA | 80kVA | 100kVA | 125kVA |
|---|---|---|---|---|---|
| Input power nom. | 40,9kVA | 68,6kVA | 91,5kVA | 114,3kVA | 142,7kVA |
| Input power max. | 49,2kVA | 75,5kVA | 100,5kVA | 126kVA | 157,3kVA |
| Current coms. nom. | 59A | 99A | 132A | 165A | 206A |
| Current coms. max. | 71A | 109A | 145A | 182A | 227A |
| Efficiency at 100% | >92% | >92% | >92% | >92% | >92% |
| Inverter-input power | 34,8kW | 52,2kW | 69,6kW | 87,1kW | 108,7kW |
| Noise level (EN 50091) | <55dB(A) | <55dB(A) | <55dB(A) | <55dB(A) | <55dB(A) |
| Heat dissipation | 2,8kW | 4,2kW | 5,6kW | 6,9kW | 8,7kW |
| Cabinets using batt. 10min | 2 | 2 | 2 | 2 | 3 |
| Weight incl. batt. for 10min. | 921kg | 1493kg | 1553kg | 1772kg | 2546kg |
| Cabinets using batt. 30min. | 3 | 3 | 3 | 4 | 4 |
| Weight incl. batt. 30min. | 1273kg | 2283kg | 2436kg | 3360kg | 3430kg |
| Weight UPS without battery | 390kg | 610kg | 670kg | 710kg | 780kg |
- Our company has the right to change the product specification,all of the products are subject to change without prior notice.