Skip to content
Passive Harmonic Filter XR Series

Harmonic Filter

Passive Harmonic Filter XR Series

Model: Passive Harmonic Filter XR Series

Solves harmonic interference from six-pulse equipment with no resonance risk, reducing THID to as low as 5%.

  • Full-load efficiency above 97%
  • Superior harmonic elimination
  • THID reduced to 5%–12%
  • Capacity 3HP to 1200HP

Specifications

Item Value
Load Type Six-pulse rectifier equipment
Capacity Range 3HP (2.2kW) to 1200HP (900kW)
Frequency 50HZ or 60HZ (±0.75HZ)
Full-load Efficiency Above 97%
System Voltage Range Three phase 208, 220, 380, 440, 480 and 600 volts (±10%)
Line Voltage Unbalance Maximum 1%
Effective Source Impedance 1.5% ~ 6.0%
Service Factor 1.0 (maximum fundamental load current rating)
Harmonic Improvement (THID) 8% or 12% THID (all operating conditions at 0~100% load); 5% THID (at 100% load)
Power Factor (full load) From 0.98 lagging to 0.98 leading; 0.95 leading at 80% load
Internal Conductors Copper
Insulation System Inductive components H class (180°C or better)
Cooling Forced fan cooling required
Enclosure Options Independent enclosure, open panel construction (can be integrated with a drive in one cabinet), or no enclosure (components for self-installation)
Ambient Temperature −40°C to +45°C (installed in switchboard)
Temperature Rise Inductive components 115°C
Maximum Altitude 1000 m
Design Standards BS G5/3, EN 61000-3-4, AS-2279, IEEE-519

Applications

  • Applied to single or multiple six-pulse variable frequency drives.
  • Low-frequency harmonic environments created by three-phase six-pulse rectifier loads, including the 5th, 7th, 11th, 13th, 17th, 19th, 23rd and 25th harmonics.
  • Other rectifier loads made up of six-pulse three-phase diode or silicon-controlled rectifiers.
  • Industrial and commercial distribution systems that need better power quality and to keep most input harmonic currents from reflecting back into the power system.

Product Features

  • Non-wave-trap design: No system analysis is required, and performance is unaffected by system impedance, load or harmonics.
  • Excellent harmonic suppression: Handles the low-frequency harmonics produced by three-phase six-pulse rectifier loads; at full load, current and voltage harmonic distortion meet the limits defined by IEEE-519, delivering 5%–12% THID.
  • High stability and safety: No need to tune the filter's resonant frequency or adjust variable capacitors, inductors or other components. The series passive structure is a low-pass filter made of inductors and capacitors plus damping resistors, providing excellent protection against filter over-excitation and resonance; it does not resonate with the power system.
  • No mutual interference: Other harmonic loads connected upstream are not absorbed by the filter, and there is no interaction with other harmonic mitigation equipment on the power system.
  • High quality and international standards: The entire series is ISO 9000 certified and fully tested before shipment. Products are designed and manufactured to international harmonic standards including BS G5/3, EN 61000-3-4, AS-2279 and IEEE-519.
  • Flexible installation and cooling: Choose an independent enclosure or an open panel construction integrated with the drive in a single cabinet. Forced fan cooling is required, and all internal filter connections use copper conductors.

Specification

  • The load is six pulse rectifier equipment
  • Capacity: From 3HP (2.2kW) to 1200HP (900kW)
  • Frequency: 50HZ or 60HZ (+/- 0.75HZ)
  • Full load efficiency: More than 97%
  • The range of system voltage: Three phase208、220、 380、440、480 and 600 volts (+/- 10%)
  • Maximum of the unbalance of circuit voltage is 1%
  • Effective source resistance: 1.5%~6.0%
  • Service Factor: 1.0(Maximum rated load current )
  • 8% THID or 12% THID ( Under the condition of 0%~100% load);5% THID(Under the condition of 100% load)
  • Under condition of full load,Power Factor of the harmonic filter will from 0.98 lagging PF to 0.98 leading PF,and while 80% load will be 0.95 leading PF
  • All of the conductors connected with filters are made of copper
  • The insulation of the inductance component is H class(180°C or more higher)
  • Heat inside the structure must be cold down by the fan
  • Enclosure: Independent enclosure or the open design that converter can integrate with our product
  • Ambient temperature: -40℃~45℃(Installed in switchboard)
  • Temperature rise: Inductance component 115℃
  • Maximum altitude: 1000 Meter

Need a customized power solution?