Harmonic Filter
Passive Harmonic Filter XR Series
Model: Passive Harmonic Filter XR Series
Solves harmonic interference from six-pulse equipment with no resonance risk, reducing THID to as low as 5%.
- Full-load efficiency above 97%
- Superior harmonic elimination
- THID reduced to 5%–12%
- Capacity 3HP to 1200HP
Specifications
| Item | Value |
|---|---|
| Load Type | Six-pulse rectifier equipment |
| Capacity Range | 3HP (2.2kW) to 1200HP (900kW) |
| Frequency | 50HZ or 60HZ (±0.75HZ) |
| Full-load Efficiency | Above 97% |
| System Voltage Range | Three phase 208, 220, 380, 440, 480 and 600 volts (±10%) |
| Line Voltage Unbalance | Maximum 1% |
| Effective Source Impedance | 1.5% ~ 6.0% |
| Service Factor | 1.0 (maximum fundamental load current rating) |
| Harmonic Improvement (THID) | 8% or 12% THID (all operating conditions at 0~100% load); 5% THID (at 100% load) |
| Power Factor (full load) | From 0.98 lagging to 0.98 leading; 0.95 leading at 80% load |
| Internal Conductors | Copper |
| Insulation System | Inductive components H class (180°C or better) |
| Cooling | Forced fan cooling required |
| Enclosure Options | Independent enclosure, open panel construction (can be integrated with a drive in one cabinet), or no enclosure (components for self-installation) |
| Ambient Temperature | −40°C to +45°C (installed in switchboard) |
| Temperature Rise | Inductive components 115°C |
| Maximum Altitude | 1000 m |
| Design Standards | BS G5/3, EN 61000-3-4, AS-2279, IEEE-519 |
Applications
- Applied to single or multiple six-pulse variable frequency drives.
- Low-frequency harmonic environments created by three-phase six-pulse rectifier loads, including the 5th, 7th, 11th, 13th, 17th, 19th, 23rd and 25th harmonics.
- Other rectifier loads made up of six-pulse three-phase diode or silicon-controlled rectifiers.
- Industrial and commercial distribution systems that need better power quality and to keep most input harmonic currents from reflecting back into the power system.
Product Features
- Non-wave-trap design: No system analysis is required, and performance is unaffected by system impedance, load or harmonics.
- Excellent harmonic suppression: Handles the low-frequency harmonics produced by three-phase six-pulse rectifier loads; at full load, current and voltage harmonic distortion meet the limits defined by IEEE-519, delivering 5%–12% THID.
- High stability and safety: No need to tune the filter's resonant frequency or adjust variable capacitors, inductors or other components. The series passive structure is a low-pass filter made of inductors and capacitors plus damping resistors, providing excellent protection against filter over-excitation and resonance; it does not resonate with the power system.
- No mutual interference: Other harmonic loads connected upstream are not absorbed by the filter, and there is no interaction with other harmonic mitigation equipment on the power system.
- High quality and international standards: The entire series is ISO 9000 certified and fully tested before shipment. Products are designed and manufactured to international harmonic standards including BS G5/3, EN 61000-3-4, AS-2279 and IEEE-519.
- Flexible installation and cooling: Choose an independent enclosure or an open panel construction integrated with the drive in a single cabinet. Forced fan cooling is required, and all internal filter connections use copper conductors.
Specification
- The load is six pulse rectifier equipment
- Capacity: From 3HP (2.2kW) to 1200HP (900kW)
- Frequency: 50HZ or 60HZ (+/- 0.75HZ)
- Full load efficiency: More than 97%
- The range of system voltage: Three phase208、220、 380、440、480 and 600 volts (+/- 10%)
- Maximum of the unbalance of circuit voltage is 1%
- Effective source resistance: 1.5%~6.0%
- Service Factor: 1.0(Maximum rated load current )
- 8% THID or 12% THID ( Under the condition of 0%~100% load);5% THID(Under the condition of 100% load)
- Under condition of full load,Power Factor of the harmonic filter will from 0.98 lagging PF to 0.98 leading PF,and while 80% load will be 0.95 leading PF
- All of the conductors connected with filters are made of copper
- The insulation of the inductance component is H class(180°C or more higher)
- Heat inside the structure must be cold down by the fan
- Enclosure: Independent enclosure or the open design that converter can integrate with our product
- Ambient temperature: -40℃~45℃(Installed in switchboard)
- Temperature rise: Inductance component 115℃
- Maximum altitude: 1000 Meter